Amps, volts, watts, and kilowatts

Amperes measure electric current. Volts measure electric potential difference. Watts measure real power: the rate at which electrical energy is converted into work, heat, light, or another useful form. A kilowatt is 1,000 watts.

Current by itself is not enough to calculate power. Ten amperes at 12 volts and ten amperes at 240 volts describe very different power levels. The calculator therefore requires voltage in every mode.

1 W = 1 A × 1 V   |   1 kW = 1,000 W

Choose the formula that matches the system

DC

For direct current, multiply current by the voltage across the load.

P(W) = I(A) × V(V)

Single-phase AC

Use RMS current and RMS voltage, then multiply apparent power by the load's power factor.

P(W) = I(A) × V(V) × PF

Balanced three-phase AC, line-to-line voltage

Use line current and line-to-line RMS voltage. The square-root-of-three factor belongs to this balanced line-to-line relationship.

P(W) = √3 × I(A) × VLL(V) × PF

Do not apply this three-phase formula to a line-to-neutral voltage. This calculator intentionally supports the line-to-line case only.

Why AC needs power factor

In AC systems, volt-amperes (VA) describe apparent power while watts describe real power. Power factor is real power divided by apparent power. A power factor of 0.80 means the real-power result is 80% of the apparent-power value represented by the selected formula.

The calculator never silently assumes a power factor of 1. If the value is unknown, use the nameplate, manufacturer data, or an appropriate measurement. Guessing it would make the real-watt result look more certain than the inputs justify.

Worked examples

DC

10 A at 12 V

10 A × 12 V = 120 W, or 0.120 kW.

1φ

10 A at 120 V and 0.80 PF

10 A × 120 V = 1,200 VA. Multiplying by 0.80 gives 960 W, or 0.960 kW.

3φ

10 A at 400 V line-to-line and 0.85 PF

√3 × 10 A × 400 V = about 6,928 VA. Multiplying by 0.85 gives about 5,889 W.

Common conversion mistakes

  • Trying to convert amps to watts without voltage.
  • Using a DC formula for an AC load with a power factor below 1.
  • Calling volt-amperes watts without applying power factor.
  • Using line-to-neutral voltage in the three-phase line-to-line formula.
  • Using peak values where the formula expects RMS AC measurements.
  • Rounding inputs before the calculation instead of rounding only the displayed result.

Methodology, assumptions, and safety limits

The engine converts entered milliamperes to amperes and kilovolts to volts, calculates at full floating-point precision, and rounds only for display. DC returns real power. AC returns apparent power in VA and real power in watts using the power factor entered by the user. Three-phase mode assumes a balanced system and explicitly interprets voltage as line-to-line RMS voltage.

The National Institute of Standards and Technology identifies the volt relationship as 1 V = 1 W/A, which is equivalent to 1 W = 1 A × 1 V. This page states every additional AC phase and power-factor assumption alongside its formula.

This is a power-conversion calculator, not a wire-size, breaker-size, service-load, motor-starting, demand-factor, voltage-drop, or code-compliance tool. Do not use the result alone to select conductors or overcurrent protection. Verify equipment ratings and system measurements, and use a qualified electrical professional for installation or safety decisions.

Last reviewed: October 9, 2026. Results depend on the entered operating current, voltage type, phase configuration, and power factor.